• 목록
  • 아래로
  • 위로
  • 0
  • 로스타
  • 조회 수 3201


Closed Tank Liquid Level(with wet leg)

DPT의 High Pressure Connection이 압력용기의 하부에 접속시 다음과 같다.




xx1.png 

 P1 :Drum Pressure

(               )kg/cm2G.

rw :Density of saturated water

(               )g/cm3AT P

rs :Density of saturated steam

(               )g/cm3AT P

ro :Density of reference LEG

(               )g/cm3AT 20 C

H :Length of reference LEG

(               ) mm

h :Measuring range

(               ) mm

h1 :Length between lower tap and 0% level

(               ) mm

h2 :Length between uper tap and 100% level

(               ) mm

Ph :High pressure of D/P cell

PL :Low pressure of D/P cell



The following equation will be consisted from the above conditions.

PL = P1 + ( H x ro ) = P1 + ( h1 + h + h2 ) x ro

Phmin = P1 + ( h1 x rw ) + ( h + h2 ) x rs

Phmax = P1 + ( h1 + h ) x rw + ( h2 x rs )



Therefore

DP o  = Phmin      -       PL

        = h x ( rs - ro ) + h1 x ( rw - ro ) + h2 x ( rs - ro )

        = (           0) x (          0) - (           0)

        =              0  mmH2O



DP100  = Phmax      -      PL

           = h x ( rw - ro ) + h1 x ( rw - ro ) + h2 x ( rs - ro )

           = (         0) x (          0) - (           0)

           =           0  mmH2O


Then, the calibration of D/P cell shall be done as following.



            DP = DP o ~ DP100 mmH2O

            =                 ~             mmH2O




밀폐탱크의_DPT_Range_계산.pdf

공유

facebooktwitterpinterestbandkakao story
퍼머링크

첨부 2

  1. xx1.png
    (File Size: 5.3KB/Download: 0)
  2. 밀폐탱크의_DPT_Range_계산.pdf
    (File Size: 27.5KB/Download: 0)

댓글 0

권한이 없습니다.